DEMU rebar coupler systems for reinforcing steel meet the requirements of BRL 0504. The alignment, cutting and bending of the male connector bars and female socket bars meet the requirements of section 2 of BRL 0503 “Tack welded reinforcement mesh, reinforcing structures and bending and interweaving”. The reinforcing steel of these connectors is of FeB 500 HWL and FeB 500 HK meets the requirements of section 2 of BRL 0501 “Reinforcing steel” and hence of section 3 “Glossary of terms” and section 5 “Requirements of NEN 6008".
See our KOMO productcertificate K-7044. category 1 for mainly statical loaded concrete constructions. See our KOMO Productcertificate K53316, category 2 applicable in dynamic loaded concrete constructions
In NEN 6008 (July 2008) the quality indicators HWL, HK and HKN are invalid and now there are ductility classes A, B and C introduced. were introduced. Applied reinforcing steel has the quality B500B or B500C. The DEMU rebar coupler system is also authorised by the German building authorities, Zulassung Nr. Z-1.5-139. female socket bars 4010 in combination with male connector bars 2020 (or 2020P)
The DEMU rebar coupler system is ideal for 100% load-bearing through fastenings in reinforcing steel.
4030 is made up of reinforcing steel with a connector at either end. 4035 is made up of reinforcing steel with on one side a connector and one side rolled thread. 2040 is made up of reinforcing steel with rolled thread at either end.
system description
Tightening torque according to Komo product certificate k-7044-09
DEMU supplies a torque wrench for the correct tightening torque ØD 12 16 20 25 32 40 Nm 75 100 160 250 400 400 Tolerance tightening torque +/- 5 %
strength
All joints may be used in tensile, compressive and shear applications. The male connector bars must be tightened to the prescribed torque (Nm). In order to determine the working value for strength of the steel in the anchor, a material factor ym must be applied to the elastic limit. See NEN 6720 section 6.2 “Reinforcing steel”. To determine the minimum anchorage length, please refer to NEN 6720 section 9.6 “Length of reinforcing steel anchorages". The type 4010 is suitable for through fastening in combination with DEMU type 2020 and with 2020-P and for constructive anchores. The 4010 female socket bar anchors must always be checked in accordance with NEN 6720 section 9.6 “Length of reinforcing steel anchorages.” and 9.16 “Embedded anchors”.
DEMU rebar coupler system is developed for making mechanical connectors with KOMO certificated reinforcing steel, quality FeB 500 HWL and FeB 500 HK in conformity with NEN 6008. The system is applicable in category 1: mainly statically loaded constructions conform BRL 0504. The DEMU rebar coupler system is tested with a tension ripple of 2 óa = 60 N/mm² at 2 million tension changes and an upper tension of 0.6 Re:k.
In NEN 6008 (July 2008) the quality indicators HWL, HK and HKN are invalid and now there are ductilityclasses A, B, and C introduced. Applied reinforcing steel has the quality B500B or B500C.
Assembly
To fasten the shuttering of type 4010 (and 2010 round 40) use can be made of various accessories including types 2250, 2280 and 2600. The plastic sealing cap type 2244 forms protection against penetrating dirt and concrete water. For extra protection we also advise greasing the internal screw thread.
working instructions
The female socket bars and male connector bars must be stored free of dirt so they can be screwed into each other without problems. The accessories ensure protection besides fixing to the shuttering. For further protection against penetrating dirt and concrete water we also advise greasing the inside of the connector. The male connector bars must be turned in using a torque wrench set to the correct tightening torque.
length of connector
You can find the length of the connector of a 4010, 2020 round 40 and a 3010 (A4-80) at FAQ, general point 6.
|